Using the menu for advanced features
Carrier Connect™ Wi-Fi Thermostat 33CONNECTSTAT43FX CARRIER CORPORATION ©2021
Installation Guide All rights reserved
22
To adjust occupancy settings
Setting
Default/Range
SET OCC FANOperates the fan in AUTO or ON during occupied periods
NOTE If the installer configured the thermostat for non-programmable operation and
remote occupancy is disabled, this setting is not available.
REMINDER! The AUTO setting is a violation of ASHRAE 90.1 and Title 24 but is a
feature of the thermostat for building owners that mandate auto fan operation during
occupied periods for energy conservation purposes.
D:
R:
AUTO
AUTO
ON
SET UNOC FANOperates the fan in AUTO or ON during unoccupied periods
NOTE If the installer has configured the thermostat for non-programmable operation
and remote occupancy is disabled, this setting is not available.
D:
R:
AUTO
AUTO
ON
UNOCC COOLThe cool setpoint during unoccupied periods
NOTES
The minimum value you can set is limited by the unoccupied heat setpoint (cool
setpoint cannot be less than the heat setpoint) and the installer setting for MIN
COOL SETPOINT.
If the installer has configured the thermostat for non-programmable operation and
remote occupancy is disabled, this setting is not available.
D:
R:
85°F
52 to 90°F
UNOCC HEATThe heat setpoint during unoccupied periods
NOTES
The maximum value is limited by the unoccupied cool setpoint (heat setpoint cannot
be greater than the cool setpoint) and the installer setting for MAX HEAT SETPOINT.
If the installer has configured the thermostat for non-programmable operation and
remote occupancy is disabled, this setting is not available.
D:
R:
62°F
50 to 88°F
OCC COOLThe cool setpoint during occupied periods
NOTES
The minimum value is limited by the occupied heat setpoint (cool setpoint cannot
be less than the heat setpoint) and the installer setting for MIN COOL SETPOINT.
If the installer has configured the thermostat for non-programmable operation and
remote occupancy is disabled, this setting is not available.
D:
R:
75°F
52 to 90°F
OCC HEATThe heat setpoint during occupied periods
NOTES
The maximum value is limited by the occupied cool setpoint (heat setpoint cannot
be greater than the cool setpoint) and the installer setting for MAX HEAT SETPOINT.
If the installer has configured the thermostat for non-programmable operation and
remote occupancy is disabled, this setting is not available.
D:
R:
70°F
50 to 88°F

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Carrier Connect 33CONNECTSTAT43FX and is the answer not in the manual?

Carrier Connect 33CONNECTSTAT43FX Specifications

General IconGeneral
BrandCarrier
ModelConnect 33CONNECTSTAT43FX
CategoryThermostat
LanguageEnglish

Related product manuals