To test the HVAC system
The installer uses this setting to test the HVAC system.
1 Press SELECT to open INSTALLER TEST.
NOTE The HOME and SELECT buttons are replaced with MODE and CANCEL buttons.
.
2 Press MODE to cycle through OFF, COOL, HEAT, and EHEAT.
NOTES
The availability of the modes are based on the installer configuration settings.
The selected MODE operates each equipment stage for 3 minutes.
The center of the display counts down the number of seconds remaining for the current stage of
equipment operation.
When the countdown reaches zero, if another stage exists, the banner text changes to 2ND STAGE and a
new 180-second countdown timer starts. If no other stage exists, the test cycle ends and the MODE is
set to OFF.
When HEAT or EHEAT modes are running and there is a configured humidifier, the output that controls
the humidifier is energized.
When COOL mode is running and a dehumidifier has been configured for operating a HumidiMiZer™, the
output configured for the dehumidifier output is energized.
3 Press CANCEL to turn off the currently running equipment and transition the screen to the installer menu
selections.
After 20 minutes of inactivity (no button presses by the installer), INSTALLER TEST terminates, and the home
screen displays.
NOTES
EHEAT is only a choice when a heat pump is selected in the configuration.
HEAT is not available in a cooling-only configuration.
COOL is not available in a heating-only configuration.