Appendix A: BACnet Points List
Carrier Connect™ Wi-Fi Thermostat 33CONNECTSTAT43FX CARRIER CORPORATION ©2021
Installation Guide All rights reserved
55
Point Name
Point Access
Units
BACnet Point Name
BACnet
Object ID
1=C°
Fan On with W
GATED_WRITE
0=NO
1=YES
FAN_WITH_W
BV:504
Rvs Vlv Energized Ht
GATED_WRITE
0=ENERGIZED FOR COOL
1=ENERGIZED FOR HEAT
RVS_VLV_DIR
BV:505
Humidifier Installed
GATED_WRITE
0=NO
1=YES
HUM_INST
BV:506
BMS Occupancy Enable
GATED_WRITE
0=DISABLED
1=ENABLED
BMS_OCC_EN
BV:507
BACnet Config Write Enable
GATED_WRITE
0=DISABLED
1=ENABLED
CFG_WR_EN
BV:511
ID TEMP SENSOR HIGH
READ_ONLY
0=DISABLED
1=ENABLED
ID_TEMP_SENS_HI
BV:900
ID TEMP SENSOR LOW
READ_ONLY
0=INACTIVE
1=ACTIVE
ID_TEMP_SENS_LO
BV:901
REMOTE SENSOR HIGH
READ_ONLY
0=INACTIVE
1=ACTIVE
REM_TEMP_HI
BV:902
REMOTE SENSOR LOW
READ_ONLY
0=INACTIVE
1=ACTIVE
REM_TEMP_LO
BV:903
HUM TEMP SENSOR HIGH
READ_ONLY
0=INACTIVE
1=ACTIVE
HUM_TEMP_HI
BV:904
HUM TEMP SENSOR LOW
READ_ONLY
0=INACTIVE
1=ACTIVE
HUM_TEMP_LO
BV:905
ID TEMP RANGE HIGH
READ_ONLY
0=INACTIVE
1=ACTIVE
ID_TEMP_RNG_HI
BV:906
ID TEMP RANGE LOW
READ_ONLY
0=INACTIVE
1=ACTIVE
ID_TEMP_RNG_LO
BV:907
HUM SENSOR FAILURE
READ_ONLY
0=INACTIVE
1=ACTIVE
HUM_SENS_FAIL
BV:908
HUMIDITY RANGE HIGH
READ_ONLY
0=INACTIVE
1=ACTIVE
HUM_TOO_HI
BV:909
HUMIDITY RANGE LOW
READ_ONLY
0=INACTIVE
1=ACTIVE
HUM_TOO_LO
BV:910
OUTDOOR SENSOR FAILURE
READ_ONLY
0=INACTIVE
1=ACTIVE
OD_TEMP_FAIL
BV:911
NOT CONNECTED TO
SERVER
READ_ONLY
0=INACTIVE
1=ACTIVE
SRVR_CONN_FAIL
BV:912
NOT CONNECTED TO
ROUTER
READ_ONLY
0=INACTIVE
1=ACTIVE
RTR_CONN_FAIL
BV:913
WIFI HARDWARE FAULT
READ_ONLY
0=INACTIVE
1=ACTIVE
WIFI_CONF_FAIL
BV:914
ECONOMIZER FAULT
READ_ONLY
0=INACTIVE
1=ACTIVE
ECON_FAULT
BV:915
LOCKOUT-5 BAD PIN
ENTRIES
READ_ONLY
0=INACTIVE
1=ACTIVE
LOCKOUT_FAIL
BV:916
Current Mode Status
READ_ONLY
1=OFF
2=HEAT
3=COOL
CURRENT_MODE
MSV:300
User Mode
READ_WRITE
1=OFF
2=HEAT
3=COOL
USER_MODE
MSV:400