SYS_STAT 12H 29 //MAINMENU/MAINTAIN/
1 sys_ctlm 0 - System Control Mode
2 sys_stat 0 - System Status
3 mas_stat 0 - Master Run Status
4 sla_stat 0 - Slave Run Status
5 sys_perl 0 % System Percent Load
6 sys_kw 0 KW System KW
7 sys_ctlp 0 °F System Control Point
8 sys_dem 0 % System Demand Limit
9 sys_supt 0 Supply Liquid Temp
10 sys_rent 0 Return Liquid Temp
ISM_CAL1 12H 31 //MAINMENU/MAINTAIN/
1 0 - J8B 4-20mA Output
2 cal_en 0 to 1 0 - Calibration Enable 0 1 x
3 ism_ma 4 to 20 4 mA ISM Output mA 4 20 x
4 ismo_per 0 to 100 0 % ISM Output Percent 0 100
5 vfd_ma 4 to 20 4 mA VFD Reading mA 4 20 x
6 vfdi_per 0 to 100 0 % VFD Reading Percent 0 100
7 cal_fact 0 to 2000 0 - Calibration Factor 0 2000
8 cal_done 0 to 1 0 - Calibration Completed 0 1
ISM_CAL2 12H 32 //MAINMENU/MAINTAIN/
1 0 - J6 0-10V Input
2 cal_en 0 to 1 0 - Calibration Enable 0 1 x
3 vfd_v 0 to 10 0 Volts VFD Output Voltage 0 10 x
4 vfdo_per 0 to 100 0 % VFD Output Percent 0 100
5 ism_v 0 to 10 0 Volts ISM Reading Voltage 0 10 x
6 ismi_per 0 to 100 0 % ISM Reading Percent 0 100
7 cal_fact 800 to 1200 1000 - Calibration Factor 800 1200
8 cal_done 0 to 1 0 - Calibration Completed 0 1
VFD_STAT 12H 34 //MAINMENU/
1 cycle_1 no/yes - Single Cycle Dropout
2 lineim_i no/yes - Line Current Imbalance
3 hi_volt no/yes - High Line Voltage
4 low_volt no/yes - Low Line Voltage
5 lo_dcbus no/yes - Low DC Bus Voltage
6 hi_dcbus no/yes - High DC Bus Voltage
7 vfd_por no/yes - VFD Power On Reset
8 grnd_t - Ground Fault
9 ph_rev no/yes - Line Phase Reversal
10 motor_ov no/yes - Motor Overload Trip
11 start_ok no/yes - Start Complete
12 rect_pu no/yes - Rectier Power Fault
13 inv_pu no/yes - Inverter Power Fault
14 rect_oi no/yes - Rectier Overcurrent
15 inv_oi no/yes - Inverter Overcurrent
16 prs_trip no/yes - Condenser High Pressure
17 no_amps no/yes - Motor Amps Not Sensed
18 accelt no/yes - Motor Acceleration Fault
19 stop_ok no/yes - Stop Complete
20 ampstop no/yes - Stop Fault
21 rect_ot no/yes - Rectier Overtemp
22 inv_ot no/yes - Inverter Overtemp
23 motim_i no/yes - Motor Current Imbalance
24 lineim_v no/yes - Line Voltage Imbalance