70
VFD_STAT 12H 34 //MAINMENU/
25 freqt no/yes - Frequency Fault
26 vfd_comm no/yes - VFD Comm Fail
27 vfdfault no/yes - VFD Fault
28 readone no/yes - Read Cong Complete
29 strt_inh no/yes - VFD Start Inhibit
30 checksum no/yes - VFD Checksum Error
31 inot_sw no/yes - Inductor Overtemp Switch
32 incomp no/yes - Incompatibility Fault
VFD_MCFG 12H 35 //MAINMENU/MAINTAIN/
1 vfd_ct 0 to 1 0 - VFD Cong Conict 0 1
2 del_vfdc 0 to 1 0 - Delete VFD Cong 0 1 x x
3 0 to 1 - Delete=Yes, Keep=No
4 rla_load 0 to 1 200 AMPS Motor Rated Load Current
5 rla 0 to 1 200 AMPS Motor Nameplate Current
6 rlv 0 to 1 460 Volts Motor Nameplate Voltage
7 rpm 0 to 1 3000 rpm Motor Nameplate RPM
8 rlkw 0 to 1 1500 KW Motor Nameplate KW
9 comp_100 0 to 1 50 Hz Compressor Speed 100%
10 skipfrq1 0 to 1 102 Hz Skip Frequency 1
11 skipfrq2 0 to 1 102 Hz Skip Frequency 2
12 skipfrq3 0 to 1 102 Hz Skip Frequency 3
13 skipband 0 to 1 0 Hz Skip Frequency Band
14 ramp_inc 0 to 1 30 sec Increase Ramp Time
15 ramp_dec 0 to 1 30 sec Decrease Ramp Time
16 lvim_th 0 to 1 10 % Line Voltage Imbalance%
17 lvim_per 0 to 1 10 sec Line Volt Imbalance Time
18 lcim_th 0 to 1 40 % Line Current Imbalance%
19 lcim_per 0 to 1 10 sec Line Current Imbal Time
20 mcim_th 0 to 1 40 % Motor Current Imbalance%
21 mcim_per 0 to 1 10 sec Motor Current Imbal Time
22 scycd_en 0 to 1 0 - Single Cycle Dropout 0 1
23 pwm_freq 0 to 1 0 - PWM Switch Frequency 0 1
24 0 to 1 - 2KHz=0, 4KHz=1
25 res_def 0 to 1 0 - Restore Defaults 0 1
26 com_tout 0 to 1 10 sec Communication Timeout
FACTORY 13H 1 //MAINMENU/CONFIG/
1 fac_pass 0 to 65535 4444 - Factory Password 0 65535
2 chil_typ 0 to 1 0 - 1 Chiller Type 0 1
3 - 19XR6/7=0,19XR2~E/D/V=1
4 unit_typ 0 to 1 0 - Unit Type 0 1
5 - Cool Only=0, Heat Mach=1
6 refg_typ 0 to 1 0 - Refrigerant Type 0 1
7 - R134a=0, R1233zd=1
8 comp_typ 0 to 1 1 - Comp (Single=0, Dual=1) 0 1
9 cond_typ 0 to 1 0 - Cond Shell Side MAWP 0 1
10 - 185PSI=0, 300PSI=1
11 chmedium 0 to 1 0 - Chilled Medium Type 0 1
12 coun_cod 0 to 999 86 - Country Code 0 999
13 freecool 0 to 1 0 - Free Cooling Option 0 1
14 vfd_opt 0 to 4 0 - VFD Option 0 4
15 - No=0,FS VFD=1,Carrier=2
16 - Rockwell=3, Eaton=4
17 iob3_opt 0 to 1 1 - IOB3 Option(19XR2~E/D/V) 0 1
18 hyd_opt 0 to 1 0 - IOB4 Option 0 1
19 hr_opt 0 to 2 0 - Heat Reclaim Option 0 2
20 gv1_type 0 to 1 0 - Guide Vane1 Type 0 1
21 - Digital=0, Analog=1