RTU Open 41
Point Name/Description
Default/Range
Continuous Occupied Exhaust
Configures the exhaust fan control strategy (BO-8). If
Yes
,
the power exhaust runs continuously in occupied mode and is off in unoccupied mode. If
No
, the power exhaust is controlled by the
D:
Power Exhaust Setpoint.
R:
No
No/Yes
Indoor CO2 Sensor Value @min (ma)
D: The CO2 value that corresponds to a 4mA input at
the appropriate input channel.
R:
0ppm
0 to 9999 ppm
Indoor CO2 Sensor Value @max (ma)
D:
The CO2 value that corresponds to a 20mA input at
the appropriate input channel.
R:
2000 ppm
0 to 9999 ppm
Outdoor CO2 Sensor Value @min (ma)
D: The CO2 value that corresponds to a 4 mA input
at the appropriate input channel.
R:
0ppm
0 to 9999 ppm
Outdoor CO2 Sensor Value @max (ma)
D: The CO2 value that corresponds to a 20 mA input
at the appropriate input channel.
R:
2000 ppm
0 to 9999 ppm