Sequence of Operation   
 
52  RTU Open 
 
Functions 1 and 2 are configured identically. Neither input may work reliably and downstream control may be 
affected, depending on the function duplicated. The alarm clears and normal control is restored when the 
input function duplication is corrected. 
High Space Relative Humidity - The RTU Open generates this alarm when the space humidity exceeds the 
Alarm Configuration > High Space Humidity Alarm Limit setpoint for 10 minutes. This alarm is inhibited until 
the RTU runs for 15 minutes to allow for system stabilization after startup. 
Low Space Relative Humidity - The RTU Open generates this alarm when the space humidity falls below the 
Alarm Configuration > Low Space Humidity Alarm Limit setpoint for 5 minutes. This alarm is inhibited until 
the RTU runs for 5 minutes to allow for system stabilization after startup. 
High CO2 - The RTU Open  generates this alarm when the space CO2 level exceeds the Alarm Configuration > 
Occupied High CO2 Alarm Limit setpoint for 1-minute. This alarm will be inhibited until the RTU has been 
running for 2-minutes to allow for system stabilization after startup. 
Supply Fan Runtime - The RTU Open generates a this alarm when the accumulated runtime exceeds the Unit 
Configuration > Supply Fan Service Alarm Timer value (when not set to 0). This alarm is most commonly 
used to indicate an equipment maintenance interval is due. The supply fan runtime accumulator may be reset 
by setting the 
Maintenance > Reset Supply Fan Runtime Alarm to Clear, and then back to Run – 
acknowledging each selection by clicking the 
OK button when it appears. Setting Unit Configuration > Supply 
Fan Service Timer value to 0 disables the supply fan runtime alarm function. 
Compressor 1 Runtime - The RTU Open generates this alarm when the accumulated runtime exceeds the 
Unit Configuration > Compressor 1 Service Alarm Timer value (when not set to 0). This alarm is most 
commonly used to indicate an equipment maintenance interval is due. The 
Compressor 1 Runtime 
accumulator may be reset by setting the 
Maintenance > Reset Comp 1 Runtime Alarm to Clear, and then 
back to 
Run – acknowledging each selection by clicking the OK button when it appears. Setting Unit 
Configuration > Compressor 1 Service Timer value to 0 disables the Compressor 1 Runtime alarm function. 
Compressor 2 Runtime - The RTU Open generates this alarm when the accumulated runtime exceeds the 
Unit Configuration > Compressor 2 Service Alarm Timer value (when not set to 0). This alarm is most 
commonly used to indicate an equipment maintenance interval is due. The Compressor 2 runtime 
accumulator may be reset by setting the 
Maintenance > Reset Comp 2 Runtime Alarm to Clear, and then 
back to 
Run – acknowledging each selection by clicking the OK button when it appears. Setting Unit 
Configuration > Compressor 2 Service Timer value to 0 disables the Compressor 2 runtime alarm function. 
Note that this function is unavailable if the 
Service Configuration > Compressor States value is not set to Two 
Stages. 
Filter - The RTU Open generates this alarm when the accumulated runtime exceeds the Unit Configuration > 
Filter Service Alarm Timer value (when not set to 0). This alarm is most commonly used to indicate a filter 
replacement is due. Reset the filter service runtime accumulator by setting the
 Maintenance > Reset Filter 
Runtime Alarm to On, back to Off, and clicking the OK button after each setting. Setting Unit Configuration > 
Filter Service Alarm Timer value to 0 disables the filter service alarm function. 
Airside Linkage Alarm - An RTU Open may act as an air source in a zoned system. Carrier systems utilize a 
function called Linkage™ to pass data between a master zone and its air source via an MS/TP network 
connection. When the RTU Open is part of a linked system, it will indicate an airside linkage alarm if it loses 
communications with its linkage master or if it receives invalid data.