The Configuration menu gives access to a number of user-
modiable parameters such as pump conguration, schedule
menu, etc. The Conguration menu is password-protected.
To access the Conguration menu, press the Main menu button
located in the upper-left part of the Home screen, and then select
Conguration Menu.
Once all the necessary modications have been made, press the
Save button to conrm your changes or the Cancel button to exit
the screen without making modications.
System conguration override: In some cases it is possible to
override system conguration. Note that not all parameters can
be overridden by the control.
CAUTION: Since specic units may not include additional
features, some tables may contain parameters that cannot be
congured for a given unit.
5 - USER INTERFACE: MENU STRUCTURE
GENCONF – General Cong
No. Name Status Default Unit Displayed text* Description
1 ramp_sel no/yes no - Ramp Loading Select Ramp loading sequence
2 o/on_d 1 to 15 1 min Unit O to On Delay Unit OFF to ON delay
*Depends on the selected language (English by default).
PUMPCONF – Pump Conguration
No. Name Status Default Unit Displayed text* Description
1 pump_seq no/yes no - Exchanger Pump Enable Water exchanger pump is enabled
2 pump_per no/yes no - Pump Sticking Protection Pump anti-sticking protection
3 pump_loc no/yes yes - Flow Checked if Pump O Water ow is checked when the pump is o
*Depends on the selected language (English by default).
HCCONFIG – Heat/Cool Cong
No. Name Status Default Unit Displayed text* Description
1 hr_sel 0 to 3 1 - Heating Reset Select Heating Reset Select
2 0=None, 1=OAT 0 = None, 1 = OAT
3 2=Delta T, 3=4-20mA
2 = Delta T (LWT-EWT)
3 = 4-20 mA control (external temperature sensor)
4 min_th
-25.0 to 0.0
-13.0 to 32.0
-20.0
-4.0
°C
°F
Min Heating OAT Threshld Minimum OAT threshold (used for unit protection control)
5 max_th
-100.0 to 100.0
-148.0 to 212.0
100.0
212.0
°C
°F
Max Heating OAT Threshld Maximum OAT threshold (used to dene the Summer mode)
6 boil_th
-30.0 to 15.0
-22.0 to 59.0
-10.0
14.0
°C
°F
Boiler OAT Threshold Boiler OAT threshold
7 ehs_th
-5.0 to 21.1
23.0 to 70.0
5.0
41.0
°C
°F
Elec Stage OAT Threshold Electric heating stage, OAT threshold
8 ehs_back no/yes no - 1 Elec Stage For Backup One electric heating stage used for back-up
9 ehs_pull 0 to 60 0 min Electrical Pulldown Time Electrical pull-down time
10 ehs_defr no/yes no - Quick EHS For Defrost Quick EHS for defrost enabled