RESETCFG – Reset Cong
No. Name Status Default Unit Displayed text* Description
1 oathr_no
-20.0 to 51.7
-4.0 to 125.0
-10.0
14.0
°C
°F
OAT No Reset Value OAT, no reset value
2 oathr_fu
-20.0 to 51.7
-4.0 to 125.0
-20.0
-4.0
°C
°F
OAT Full Reset Value OAT, max. reset value
3 dt_hr_no
0 to 51.7
0 to 25.0
0
0
^C
^F
Delta T No Reset Value Delta T, no reset value
4 dt_hr_fu
0 to 13.9
0 to 25.0
0
0
^C
^F
Delta T Full Reset Value Delta T, max. reset value
5 I_hr_no 0 to 20 0 mA Current No Reset Value Current, no reset value
6 I_hr_fu 0 to 20 0 mA Current Full Reset Value Current, max. reset value
7 hr_deg
-30.0 to 30.0
-54.0 to 54.0
10.0
18.0
^C
^F
Heating Reset Deg. Value Heating reset value
*Depends on the selected language (English by default).
CTRLID – Control Identication
No. Status Default Displayed text* Description
1 0-239 1 CCN Element Number Element number
2 0-239 0 CCN Bus Number Bus number
3 9600 / 19200 / 38400 9600 CCN Baud Rate Communication speed
4 - 61AF Device Description Unit description
5 - - Location Description Location description
6 - - Software Version Software version
7 - - Serial Number Serial number (MAC address)
*Depends on the selected language (English by default).
FLOWCONF – 0-10V Pump Cong.
No. Name Status Default Unit Displayed text* Description
1 logictyp 0 to 2 0 - Logic: 0=No,1=STEP,2=PID
Logic type:
0 = No 0-10V external pump
1 = 0-10V External Pump controlled by Step Logic
2 = 0-10V External Pump controlled by PID Logic
2 minspeed 0 to 45 10 % Minimum Pump Speed Minimum pump speed
3 maxspeed 55 to 100 100 % Maximum Pump Speed Maximum pump speed
4 step 1 to 20 5 - Pump Speed Step Pump speed step
5 dt_stp
2.0 to 20.0
3.6 to 36.0
5.0
9.0
^C
^F
Water Delta T Setpoint Water delta T setpoint
6 deadband
0.5 to 2.0
0.9 to 3.6
1.0
1.8
^C
^F
Deadband (for Step ctrl) Deadband for step control
7 dt_kp -10 to 10 -2 - PID Control Prop. Gain PID control proportional gain
8 dt_ki -10 to 10 -0.2 - PID Control Integ. Gain PID control integrative gain
9 dt_kd -10 to 10 0 - PID Control Deriv. Gain PID control derivative gain
10 timer 1 to 60 10 sec Reschedule Timer
Reschedule timer (delay before the new calculation is made
– used for both Step and PID logic control)
*Depends on the selected language (English by default).
ADD_OPT – Add Options
No. Displayed text* Description
1 MAC Address
Controller MAC address: This MAC address is requested by your local service representative
when ordering any software-protected option (see also section 6.12)
2 Please Enter Your Software Activation Key Software Activation Key provided by a service technician (see also section 6.12)
3 Unit must be O󰀨 The unit should not be operating when installing the Software Activation Key
*Depends on the selected language (English by default).
NOTE: If you need to add an option, please contact your local
service representative.
5 - USER INTERFACE: MENU STRUCTURE