6 - STANDARD CONTROL OPERATIONS AND OPTIONS
6.4 - Water pump control
The unit can control one water exchanger pump which can be
either a xed speed pump or a variable speed pump.
The pump can be factory-installed (“internal pump”) or it can be
supplied by the customer (“external pump”).
Pump control logic Internal pump External pump
Constant speed control yes -
Variable speed control yes yes
The pump is normally turned on when the unit is running in Heating
mode. The pump control method may vary depending on the type
of the pump (internal or external) and the pump control logic set
by service technicians. When the unit is “O”, the pump is stopped;
however, the pump can be started in particular operating conditions
when freeze protection of the heat exchanger is active
(see section 6.4.3).
6.4.1 - Constant speed control
Fixed speed pump can be controlled through the “Pump 1 Output”
parameter in the Outputs menu. Fixed speed pump control applies
only to internal pumps.
6.4.2 - Variable speed control
The water flow is controlled based on Delta T (differential
temperature) on the water exchanger; however, the control logic
may dier depending on the type of the pump (internal/external).
Variable speed control Internal pump External pump
LEN drive yes -
0-10V drive: Step control - yes
0-10V drive: PID control optional yes
6.4.2.1 - Internal pump control
The speed of the internal pump may vary depending on the current
unit capacity and service conguration. For example, in defrost
mode higher pump speed equals better eciency; therefore, during
defrost the pump speed will be set to the maximum speed that is
allowed. At the same time, when the unit is running, but there is
no heating demand, the pump speed will be low. Under normal
operating conditions, the unit’s nominal water flow should
correspond to the minimum pump speed.
Depending on factory installation, the internal pump can be
controlled either through the standard LEN drive or the optional
0-10V drive. The internal pump control can be set only by service
technicians.
When controlled through the LEN drive:
■ The status of the internal pump is displayed in the Pump Status
menu under “Drive pump status”.
■ “External Pump Output” (PUMP_EXT, Pump Status menu) and
“External Pump Output” (PUMP_EXT, Outputs menu) will be
set to ,,0”
When controlled through the 0-10V drive:
■ The drive output is controlled through 0-10V output, i.e.
“External Pump Output” (PUMP_EXT, Outputs menu).
■ “External Pump Output” (PUMP_EXT, Pump Status menu)
displays its value in %.
■ The output is controlled by a PID to satisfy the Water Delta T
Setpoint dened by service technicians. When the unit is ready,
the pump speed is set to pump saving speed (minimum pump
speed). When the unit is running, water pump speed is clamped
between the minimum and maximum pump speed.
6.4.2.2 - External (customer) pump control
The control allows for managing the external 0-10V pump via the
0-10V Pump Cong menu (FLOWCONF).
When controlled through the 0-10V drive:
■ The pump is controlled through 0-10V output, i.e. “External
Pump Output” (PUMP_EXT, Outputs menu).
■ “External Pump Output” (PUMP_EXT, Pump Status menu)
displays its value in %.
The customer pump can be controlled by:
■ Step control logic.
- a step value is added to the output each time the “Reschedule
timer” has elapsed and Delta T > Water Delta T Setpoint
[dt_stp] + Deadband
- a step value is removed from the output each time the
“Reschedule timer” has elapsed and Delta T < Water Delta
T Setpoint [dt_stp] - Deadband
■ PID control logic. The output is controlled by a PID to satisfy
Water Delta T Setpoint.
To set 0-10V pump control method
1. Navigate to the Conguration menu.
2. Select 0-10V Pump Cong (FLOWCONF).
3. Set the pump control logic [logictyp].
Logic: 0=No,1=STEP,2=PID [logictyp]
0 = no (no external pump)
1 = Step control logic
2 = PID control logic
6.4.3 - Pump protection (pump anti-stick function)
The control provides a means to automatically start the pump each
day at 14:00 for 2 seconds when the unit is o.
Starting the pump periodically for a few seconds extends the
lifetime of the pump bearings and the tightness of the pump seal.
To set pump automatic rotation delay
1. Navigate to the Conguration menu.
2. Select Pump Conguration (PUMPCONF).
3. Set Pump Sticking Protection [pump_per] to “yes”.
Pump Sticking Protection [pump_per]
no/yes yes