EasyManua.ls Logo

Carrier VVT Zone - Page 59

Carrier VVT Zone
80 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
VVT Zone Controller 55
Unoccupied Heating 1
Light Blue
The space temperature must be less than this value for the VVT Master to consider the
zone a heating caller. The zone remains a heating caller until the space temperature
rises above the
Unoccupied Heating
setpoint. We recommend that this value be set no
lower than .5°F below the
Unoccupied Heating
D:
setpoint.
R:
54°F
40 to 99°F
Unoccupied Heating 2
D: Dark Blue
The space temperature must be less than this value before a low space temperature
alarm is generated.
R:
52°F
40 to 99°F
Unoccupied Cooling 1
Yellow
The space temperature must be greater than this value for the VVT Master to consider
the zone a cooling caller. The zone remains a cooling caller until the space temperature
drops below the
Unoccupied Cooling
setpoint. We recommend that this value be set no
lower than .5°F above the
Unoccupied Cooling
D:
setpoint.
R:
91°F
40 to 99°F
Unoccupied Cooling 2
D: Orange
The space temperature must be greater than this value before a high space
temperature alarm is generated.
R:
93°F
40 to 99°F
Point Name/Description
Range
Heating Capacity
D:
Used for Optimal Start, this is the rate at which the zone
temperature changes when the heating system runs at full capacity to maintain
designed occupied heating setpoint.
R:
5°F/hr
0 to 120°F/hr
Heating Design Temp
D:
The geographically-based outdoor air temperature at which the
heating system must run constantly to maintain comfort. This information is available
in ASHRAE publications and most design references.
R:
0°F
-100 to 150°F
Cooling Capacity
D:
Used for Optimal Start, this is the rate at which the zone
temperature changes when cooling system runs at full capacity to maintain designed
occupied cooling setpoint.
R:
5°F/hr
0 to 140°F/hr
Cooling Design Temp
The geographically-based outdoor air temperature at which the
cooling sys
tem must run constantly to maintain comfort. This information is available in
ASHRAE publications and most design references.
D:
R:
100°F
-100 to 150°F

Table of Contents

Related product manuals