Drainage
Ensure any slopes, walls, or fencing at the site do not trap water around the charging station installation
site. The system is only built to withstand water to the height of the conduit stub-up.
WARNING: Exposing the ChargePoint charging station to water above the height of the conduit
stub-up could create an electrocution, shock, or fire hazard. Cut power to the charging station if it
has been exposed to standing water and contact ChargePoint before the charging station is
powered on.
Clearances
For pedestal installations, the conduit stub-up must be a minimum of 230 mm (9 in) from any obstructions
to the rear. This includes other charging stations. Check applicable codes for any additional clearance
requirements.
Accessibility
Comply with regional accessibility laws, regulations, and ordinances. The CP6000 charging station must
not block ramps or pathways and the height of the interactive display cannot exceed the maximum height
as dictated by local laws.
Signage
Refer to local and regional code to design the following elements for the site:
l
Any required re-striping of parking spaces
l
EV or Accessible EV signs
l
EV or Accessible EV paint markings on and around the parking spaces