Correspondence table:
10.2 Pressure sensor
The high and low values for the HP/LP pressure sensors are given below:
The sensors are adjusted using parameters P30 to P39.
Measurement range:
- Power supply: 5 V DC
- Signal: 0.5 - 4.5 V
Short-circuit faults will be detected by a voltage 4.75 V.
Open-circuit faults will be detected by a voltage 0.25 V.
The pressure values given are for relative pressure.
The HP sensor will:
- Monitor the HP pressure in the circuit and relay this information
- Control the unit using the HP
- Control the condensing pressure
The LP sensor will:
- Monitor the LP pressure in the circuit and relay this information - Monitor for refrigerant leaks before turning on stages
When reading the operation parameters for the pressure levels, the sensors can be adjusted with the OK button if is a difference is
found between a value that is read and the corresponding value measured by a pressure gauge.
Example:
Press OK to access and change the adjustment value.
Press OK to confirm the new adjustment value and go back to the
operation parameter.
Press ESC to cancel any changes made and go back to the
operation parameter.
This readjustment will be used to correct the difference between the value
measured by a pressure sensor and the value read on a pressure gauge.
The resulting new slope will then be used for control.
Temperature
(°C)
SENSOR RESISTANCE Ω
DISCHARGE SENSOR
50 KΩ
CONTROL AND OUTDOOR
SENSOR 10 KΩ
10
-
55340
-5
-
42340
0
162250
32660
5
126977
25400
10
99517
19900
15
78570
15710
20
62468
12490
25
50000
10000
30
40280
8058
35
32650
6532
40
26624
5326
45
21834
4368
50
18005
3602
Low value
from
High value
to
P31
P30
HP1
P33
P32
HP2
P37
P36
LP1
P39
P38
LP2
P 3 x x H P x P R E S S U R E
x x . x b
S E N S O R A D J U S T M E N T H P x
x x . x b 0 . 0 b
[- 1 + 1] 0 by default
High value
Low value
Pressure
Voltage
Calculation
with
adjustment

Table of Contents