CIAT Connect 2 - MANAGEMENT OF THE BACK-UP BOILER; Management under normal operation; Management of the electric auxiliary heaters when the thermodynamic control stage is shut off by a setpoint corrected by the discharge protection; Management of the boiler when the machine has been shut off by a general fault

CIAT Connect 2
101 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
83
Fault message:
If a fault occurs:
- Fault stored in memory in case of a mains power failure
- Fault saved in fault memory
- Relay in On position
- Unit fault LED lit steady.
To disable this function:
- Simply press the + button until the maximum value of the parameter appears. Above this value, the following message appears:
- To turn off the function, simply press Enter.
- To re-enable it, simply enter a value of between 35°C and 50°C and press Enter.
19-3- Restriction to the maximum air temperature in heating mode:
This function is used to prohibit the machine operating in heating mode when the outdoor temperature rises above a configurable value.
This function is disabled if at least one circuit is being defrosted
Visible if P2 = water-to-water and reversible air-to-water when P119 1 (Cooling only)
- This parameter can be set to between -5°C and 20°C inC increments.
- Default setting: DISABLED
The unit shuts off once the outdoor temperature P225.2
The unit restarts once the temperature rises back to above P225.2 - 2K.
Display
This limit is not managed as a fault if the machine is shut off because of it:
- Not stored in memory if a mains power failure occurs
- Fault not saved in memory
- Fault relay in Off position
- The unit fault LED is off
To disable this function:
- Simply press the + button until the maximum value of the parameter appears. Below this value, the following message appears:
- To turn off the function, simply press Enter.
- To re-enable it, simply enter a value of between -5°C and +20°C and press Enter.
19-4- Restriction to the minimum air temperature in cooling mode:
This function is used to prohibit the machine operating in cooling mode when the outdoor temperature rises above a configurable value.
Visible if P2 = Reversible Water-to-Water and Air-to-Water when P119 2 (Heating only)
- This parameter can be set to between -20°C and 12°C in 1°C increments.
- Default setting: DISABLED
The unit shuts off once the outdoor temperature P225.3.
The unit restarts once the temperature rises back to above P225.3 + 2K.
Display
This limit is not managed as a fault if the machine is shut off because of it:
- Not stored in memory if a mains power failure occurs
- Fault not saved in memory
- Fault relay in Off position
- The unit fault LED is off.
M A C H I N E O F F I N C L G M O D E
O U T T E M P . T O O H I G H
P 2 2 5 . 1 M A X . A I R T E M P .
I N C L G M O D E D I S A B L E D
P 2 2 5 . 2 M A X . A I R T E M P .
I N H T G M O D E - x x °
M A C H I N E O F F I N H T G M O D E
O U T T E M P . T O O H I G H
P 2 2 5 . 2 M A X . A I R T E M P .
I N H T G M O D E D I S A B L E D
P 2 2 5 .3 M I N . A I R T E M P .
I N C L G M O D E + x x °
M A C H I N E O F F I N C L G M O D E
O U T T E M P . T O O L O W