9. CHECKING BEFORE COMMISSIONING
Electrical connections
Installation norms
NOTE: Under no circumstance should the unit be started without having read the brochure completely.
CONNECT2 electronic control
In order to establish the unit's electric power supply (cable inlet,
calculation of the lead section, protections etc.), refer to:
- The information supplied in this document (table of technical
characteristics).
- Data plate.
- The wiring diagram and the legend supplied with the unit.
- The electronic control brochure which is supplied with the unit.
- The regulations and norms in force which regulate the installation of
air-conditioning units and electric receivers.
The electric power supply of the unit must be sized in accordance with
the maximum power input by the unit taking into account all the options
it features (if necessary, refer to the technical brochure).
Verify that electrical power corresponds to the one on the data plate
and that the voltage remains constant.
Check that the electrical connections are correct and tight
(an electrical diagram is included with each unit, along with
its legend).
Note: All connections in the site are the responsibility of the
installer. These connections are always made as per the
current regulation.
To prevent electrical shocks, make all electrical connections
before energizing the unit. Check that the automatic switch
is closed. Omitting this can cause personal damage. Make
the ground connection before any other electrical connection.
V-220004
V-220005
The installer must fi x line protection elements according to
the effective legislation.
Models 90 to 360 (STD version)
and 90 to 280 (HEE version):
collapsible
polycarbonate
window for access
to the control panel
Door
switch
Electric
panel
Options
for outlet from
the electrical
power supply
Models 420 to 960 (STD version)
and 320 to 720 (HEE version):
CONNECT2 panel control
Options for outlet from
the electrical power supply
Door
switch
Electric
panel
System built out of a
control board and a
local control panel and
display.
Main functions:
- Control of the water's temperature.
- Possibility of three types of control:
* Deviation in the water return (default).
* PIDT in the water outlet.
* Control based on the outdoor temperature.
- Control of the operating parameters.
- Diagnosis of operating faults.
- Memorisation of errors in case of short-circuiting.
- Automatic management and equalisation of operating time of the
compressors (multi-compressors).
- Possibility of remote control (on/off, modifi cation of the setpoint
temperature, operating state, general alarm) through a remote
control (optional)
- Possibility of remote reporting of the operating states and errors
through an interface module (optional).
Note: for more detailed information on these controls, please refer to
their brochures.