Lightning and AC Power Fault Interference
If signal wires exceed recommended cabling distances, or if signal wires pass between buildings, you should
consider the effect that a lightning strike in your vicinity might have on the controller.
The electromagnetic pulse (EMP) generated by lightning or other high-energy phenomena can couple enough
energy into unshielded conductors to damage or destroy electronic equipment. If you have previously
experienced such problems, you should consult with RFI/EMI experts to ensure that you have adequate
electrical surge suppression and shielding of signal cables in your controller operating environment.
Rack-Mounting Guidelines
This section describes guidelines on rack-mounting.
Precautions for Rack-Mounting
The following rack-mounting guidelines are provided to ensure your safety:
Do not move large racks by yourself. Due to the height and weight of a rack, a minimum of two people
are required to accomplish this task.
Ensure that the rack is level and stable before extending a component from the rack.
Ensure that proper airflow is provided to the components in the rack.
Do not step or stand on any component or system when servicing other systems or components in a rack.
When mounting the controller in a partially filled rack, load the rack from the bottom to the top with the
heaviest component at the bottom of the rack.
If the rack is provided with stabilizing devices, install the stabilizers before mounting or servicing the
unit in the rack.
General Rack-Selection Guidelines
The Cisco Catalyst 9800-80 Wireless Controller can be mounted in most two-post or four-post, 19-in. equipment
racks that comply with the Electronics Industries Association (EIA) standard for equipment racks (EIA-310-D
19-in.). The rack must have at least two posts with mounting flanges to mount the chassis.
When mounting a chassis in any type of rack equipment, ensure that the inlet air to the chassis does not exceed
131°F (55°C).
Caution
The distance between the center lines of the mounting holes on the two mounting posts must be 18.31 in. ±
0.06 in. (46.50 cm ± 0.15 cm). The rack-mounting hardware included with the chassis is suitable for most
19-in. (48.3-cm) equipment racks.
Consider installing the Cisco Catalyst 9800-80 Wireless Controller in a rack with the following features:
NEBS-compliant, 19-in. (48.3-cm) wide rack.
Cisco Catalyst 9800-80 Wireless Controller Hardware Installation Guide
30
Preparing Your Site for Installation
Rack-Mounting Guidelines