Data creazione 10/09/03 DS03I009GB--00 Pagina 10 di 59
I/O CLIVETTALK.LOCAL.EX1
Connector Pin Terminal Description Note
CN1-1
CN1-2
12Vac power
12Vac power
Max. 4VA
CN1-3
CN1-4
Differential pressure switch
12V
CN1-5
CN1-6
Check system charge
12V
CN1-7
CN1-8
Safety devices pump 1
12V
CN1-9
CN1
CN1-10
Safety devices pump 2
12V
Max. 10mA for each input
CN2-1
Water inlet temperature NTC
CN2-2
Gnd
CN2-3
Water outlet temperature NTC
CN2-4
Gnd
CN2-5
Configurable NTC
CN2-6
Gnd
NTC
10k=25°C
CN2-7
Configurable 0-10 or 4-20
CN2-8
VRdd
Hardware setting
CN2-9
0-10V output
CN2
CN2-10
Gnd
0-10V
J4-1
1
J4-2
2
C
Antifreeze heater control signal
J4-3
3
J4-4
4
C
Pump 1 control signal
J4-5
5
J4
J4-6
6
C
Pump 2 control signal
5A-250V
AC1