EasyManuals Logo
Home>CLIVET>Controller>TALK

CLIVET TALK User Manual

CLIVET TALK
59 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #58 background imageLoading...
Page #58 background image
Data creazione 10/09/03 DS03I009GB--00 Pagina 58 di 59
MAINTENANCE SET POINT
The unit can be enabled to operate with a MAINTENANCE set point, which controls the water temperature
even when the unit is OFF or in Standby.
The following configuration parameters are used:
Description Limits UOM Default Pass
Enable Maintenance in Cool MantCoolEn
0 ÷ 1
Flag 0
Enable Maintenance in Heat MantHeatEn
0 ÷ 1
Flag 0
Maintenance set point in Cool SetMantCool
Maintenance set point in Heat SetMantHeat
Maintenance scan time TscanMant
No. compressors in
Maintenance
N°CompMant.
1 ÷ 4
Num 1
Pump start time TstartingPump
MantCoolEn MantHeatEn
Unit ON
NO
YES
Unit ON
YES
NO
YES
NO
Set = Current cool set YES Set = Current heat set
NO
YES
Pump = OFF Pump = OFF
NO NO
Set = SetMantCool
Start count
T = TScanMant
YES
Set = SetMantHeat
Start count
T = TScanMant
YES
NO
TScanMant ended
Start pump for
T = TstartPump
YES
NO
TStartPump ended
SetMantCool
satisfied
NO
Stop pump
YES
Start available
compressors according to
par N°CompMant.
YES
TScanMant ended
Start pump for
T = TstartPump
YES
NO
TStartPump ended
SetMantHeat
satisfied
NO
Stop pump
YES
Start available
compressors according to
par N°CompMant.
NO

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the CLIVET TALK and is the answer not in the manual?

CLIVET TALK Specifications

General IconGeneral
BrandCLIVET
ModelTALK
CategoryController
LanguageEnglish

Related product manuals