MAINTENANCE SET POINT
The unit can be enabled to operate with a MAINTENANCE set point, which controls the water temperature
even when the unit is OFF or in Standby.
The following configuration parameters are used:
Description Limits UOM Default Pass
Enable Maintenance in Cool MantCoolEn
0 ÷ 1
Flag 0
Enable Maintenance in Heat MantHeatEn
0 ÷ 1
Flag 0
Maintenance set point in Cool SetMantCool
Maintenance set point in Heat SetMantHeat
Maintenance scan time TscanMant
No. compressors in
Maintenance
N°CompMant.
1 ÷ 4
Num 1
Pump start time TstartingPump
MantCoolEn MantHeatEn
Unit ON
NO
YES
Unit ON
YES
NO
YES
NO
Set = Current cool set YES Set = Current heat set
NO
YES
Pump = OFF Pump = OFF
NO NO
Set = SetMantCool
Start count
T = TScanMant
YES
Set = SetMantHeat
Start count
T = TScanMant
YES
NO
TScanMant ended
Start pump for
T = TstartPump
YES
NO
TStartPump ended
SetMantCool
satisfied
NO
Stop pump
YES
Start available
compressors according to
par N°CompMant.
YES
TScanMant ended
Start pump for
T = TstartPump
YES
NO
TStartPump ended
SetMantHeat
satisfied
NO
Stop pump
YES
Start available
compressors according to
par N°CompMant.
NO