SECOND SET POINT FROM DIGITAL INPUT
Two different set points can be used, depending on the status of digital input 2Set. The following parameters
are used.
Description Limits UOM Default
Enable second set point
0 = NO
1 = YES
2SetEn
0 ÷ 1
Flag 0
Second set point in Cool SecondSetC
MinSetC ÷ MaxSetC
Num 8
Second set point in Heat SecondSetH
MinSetH ÷ MaxSetH
Num 35
HARDWARE:
The digital input connected to the terminals (J1-6 / J1-7) will be used to enable the operation of the unit with
the second set point. By connecting a switch or other device with voltage-free contact to the input in
question, the following situations are possible:
Contact open, COOLING or HEATING set point enabled
Contact closed, second set point enabled
NB: The change in status of the second set point enabling contact must remain stable for at least 10
seconds before the changeover becomes effective.