SET POINT CORRECTION IN COOLING
The current set point in cooling is defined by the parameter SetCool and by the following corrections:
• OutsideT correction
: Value of the correction based on the outside temperature (between 0 and
MaxCextC).
If the outside humidity probe is present, the correction of the set point will also depend on the factor
Enthalpy Ext correction
(between 0 and MaxCextC).
• WR correction
: value of the Water Reset correction according to the external signal (between 0 and
MaxCWRC).
The current set point will therefore be defined as follows:
Current set point = SetCool + OutsideT correction + WR correction
In any case, the value calculated in this way is automatically limited between the two values set for the
parameters MinSetC and MAXSetC, that is:
MinSetC > current set point < MAXSetC