Data creazione 10/09/03 DS03I009GB--00 Pagina 40 di 59
GENERAL UNIT STATUS MENU
Generals
Item Description UOM
Unit status ON-OFF status
Unit mode
Unit operating mode
Current set point
Current set point value °C
Inlet Temperature
Unit inlet temperature value °C
Outlet Temperature
Unit outlet temperature value °C
Number of active steps
Capacity-control steps currently active
Current step offset
Value, calculated by the temperature controller
based on the various active compensations, which
added to (or subtracted from, in heating) the
current set point, defines the temperature threshold
beyond which a capacity-control step can be
activated.
°C
Step activation time
Scan time for the activation of the capacity-control
steps. The temperature controller can only activate
steps when the TimeScan (see below) reaches the
value indicated here.
Step count increase
Step activation count increase.
Outside compensation
Set point compensation, calculated based on the
temperature (or enthalpy) of the outside air.
°C
WR compensation
Set point compensation, calculated based on a
Water Reset signal from an external device.
°C
Unit compensation
Load compensation calculated by the temperature
controller based on the IN-OUT temperature
difference (this compensation is added to the step
difference)
°C
Start compensation
Load compensation calculated by the temperature
controller based on some parameters that define
the optimum operation of the compressors. (This
compensation is added to the step difference)
°C
Duty compensation
Load compensation calculated by the temperature
controller based on some parameters that define
the optimum operating cycle of the compressors.
(This compensation is added to the step
difference)
°C
Outside temperature
Temperature of the outside air °C
Outside relative humidity
Relative humidity of the outside air %
FreeCooling valve percentage
Percentage of opening of the freecooling valve %
Outside FreeCooling ventilation
percentage
Percentage of the air flow-rate of any dry cooler
connected to the unit with the function of
freecooling device
%
FreeCooling valve status
Status of the freecooling On-Off valve
Pump 1 status
Status of pump 1
Pump 2 status
Status of pump 2
Water Reset
Percentage of the Water Reset signal applied to
the inlet
%
Demand Limit
Percentage of the Demand Limit signal applied to
the inlet
%