EasyManuals Logo
Home>CLIVET>Controller>TALK

CLIVET TALK User Manual

CLIVET TALK
59 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #42 background imageLoading...
Page #42 background image
Data creazione 10/09/03 DS03I009GB--00 Pagina 42 di 59
LIST OF ALARMS
CENTRAL MODULE ALARMS
Code displayed Reset Description-actions
E001 H2O IN temp. probe fault on
control module
Automatic Disable load compensation and freecooling
E002 H2O OUT temp. probe fault on
control module
Automatic Total shut-down – pump on
E003 Outside air temp. probe fault Automatic Inhibit associated functions (freecooling –
set point compensation - defrost count
times)
E004 Water Reset input fault Automatic Inhibit WR compensation
E005 Outside RH% probe fault Automatic Inhibit associated functions
E006 Thermal cut-out alarm pump 1 on
control module
Automatic See pump management
E007 Thermal cut-out alarm pump 2 on
control module
Automatic See pump management
E008 Flow switch alarm on control
module
See pump
management
Total shut-down - see pump management
E009 System pressure alarm Manual Total shut-down - see pump management
E010 Phase monitor alarm Automatic Total shut-down - Pump Off after suitable
interval
E011 Antifreeze alarm on control
module
Manual Total shut-down - Pump on
E012 Antifreeze pre-alarm on control
module
Automatic (*) Disable steps
E013 Change pump on CONTROL
MODULE
Automatic (*) Signal
E014 Unit configuration alarm Automatic (*) Signal
E015 Demand Limit input fault Automatic (*) Signal
E016 Main can net disconnectedness Automatic (*) Total shut-down

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the CLIVET TALK and is the answer not in the manual?

CLIVET TALK Specifications

General IconGeneral
BrandCLIVET
ModelTALK
CategoryController
LanguageEnglish

Related product manuals