LIST OF ALARMS
CENTRAL MODULE ALARMS
Code displayed Reset Description-actions
E001 H2O IN temp. probe fault on
control module
Automatic Disable load compensation and freecooling
E002 H2O OUT temp. probe fault on
control module
Automatic Total shut-down – pump on
E003 Outside air temp. probe fault Automatic Inhibit associated functions (freecooling –
set point compensation - defrost count
times)
E004 Water Reset input fault Automatic Inhibit WR compensation
E005 Outside RH% probe fault Automatic Inhibit associated functions
E006 Thermal cut-out alarm pump 1 on
control module
Automatic See pump management
E007 Thermal cut-out alarm pump 2 on
control module
Automatic See pump management
E008 Flow switch alarm on control
module
See pump
management
Total shut-down - see pump management
E009 System pressure alarm Manual Total shut-down - see pump management
E010 Phase monitor alarm Automatic Total shut-down - Pump Off after suitable
interval
E011 Antifreeze alarm on control
module
Manual Total shut-down - Pump on
E012 Antifreeze pre-alarm on control
module
Automatic (*) Disable steps
E013 Change pump on CONTROL
MODULE
Automatic (*) Signal
E014 Unit configuration alarm Automatic (*) Signal
E015 Demand Limit input fault Automatic (*) Signal
E016 Main can net disconnectedness Automatic (*) Total shut-down