Data creazione 10/09/03 DS03I009GB--00 Pagina 38 di 59
Controls Dripping time
Add Code Description UOM Pass
17/CEN DeltaTC Design temperature difference in cooling °C 1
18/CEN DeltaTH Design temperature difference in heating °C 1
19/CEN IsLastStep Hysteresis to stop last active step °C 1
20/CEN IsFirstStep Hysteresis to start first step °C 1
109/CEN TScanMax Maximum step activation scan time Sec 2
116/CEN TScanMin Minimum step activation scan time Sec 2
120/CEN TSRelease Step deactivation scan time Sec 2
274/CEN TScanRecovery Recovery activation scan time Sec 2
Controls Set Point
Add Code Description UOM Pass
6/CEN Set2EN Enable second set point function 1
86/CEN MaxSetHeat Maximum limit allowed for the heating set point °C 1
87/CEN MinSetHeat Minimum limit allowed for the heating set point °C 1
88/CEN MaxSetCool Maximum limit allowed for the cooling set point °C 1
89/CEN MinSetCool Minimum limit allowed for the cooling set point °C 1
90/CEN SecondSetC Second cooling set point °C 0
91/CEN SecondSetH Second heating set point °C 0
118/CEN SetCool Cooling set point °C 0
119/CEN SetHeat Heating set point °C 0
272/CEN SetRecovery Recovery set point
273/CEN BandRecovery Temperature difference for recovery set point
Controls Water reset
Add Code Description UOM Pass
11/CEN MaxCWRC Maximum value of water reset correction in cooling °C 1
24/CEN MaxCWRH Maximum value of water reset correction in heating °C 1
75/CEN WaterReset Enable the Water Reset function 1
102/CEN SWRMaxH Signal corresponding to maximum correction in heating % 1
104/CEN SWRMinH Signal corresponding to minimum correction in heating % 1
105/CEN SWRMaxC Signal corresponding to maximum correction in cooling % 1
108/CEN SWRMinC Signal corresponding to minimum correction in cooling % 1