The freecooling phase is enabled
(starts) if:
a) The temperature of the outside air is less than:
Current set point + DeltaFC.
b) The return water temperature from the system (measured by probe BT1 located at the inlet to
the FC coil) is higher than:
Outside air temperature + IstStopFC
The freecooling phase is disabled
(stops) if:
c) The temperature of the outside air exceeds:
Current set point + DeltaFC + IstStopFC
d) The return water temperature from the system (measured by the NTC probe located at the inlet
to the FC coil) falls below the outside air temperature.
Toutside < (Current Set Point + DeltaFC)
YES
NO
T
inlet
> (T
outside
+
lstStopFC
)
YES NO
Tinlet < Toutside
YES NO
Stop FC
is at least
one compressor ON?
YES NO
start FC
at 100%
start FC and modulate
according to Toutaverage
YES
NO
Stop FC
Toutside > (Current Set Point + DeltaFC + IstStopFC)