Data creazione 10/09/03 DS03I009GB--00 Pagina 8 di 59
Connector Pin Terminal Description Note
J17-1
H
J17-2
L
J17
J17-3
GND
CAN OPEN
J18-1
30
J18-2
31
NTC input, outside air temperature
Gnd
J18-3
32
J18-4
33
NTC input, water temperature OUT 1
Gnd
J18-5
34
J18-6
35
NTC input, water temperature IN
Gnd
NTC
10K=25°C
J18-7
36
J18
J18-8
37
+15V
4-20mA input, outside RH%
4-20mA
J19-1
38
J19-2
39
J19-3
40
+15V
Demand Limit input
Gnd
4-20mA or 0-10V
from parameter
J19-4
41
J19-5
42
J19
J19-6
43
+15V
Water reset input
Gnd
4-20mA or 0-10V
from parameter
J20-1
44
J20-2
45
Freecooling proportional valve output
Gnd
0-10V
J20-3
46
J20
J20-4
47
Ext Free Cool proportional vent. output
Gnd
0-10V