EasyManuals Logo

CLIVET WDAT-SL3 FC Series User Manual

CLIVET WDAT-SL3 FC Series
70 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #22 background imageLoading...
Page #22 background image
22 WDAT-SL3 FC 200.2-580.2 M08S40E15-01
6.11 Climatic TExt
Menu accessible only after having entered the password.
Access reserved only to specically trained personnel.
The parameter modication can cause irreversible damages.
The setpoint dened by the temperature curve is shown at status S0010: ActualSptTExt
Only if P0053: En Climatica ≠ 0
Path: Main Menu / Unit parameters / Climatica TExt
Example
Step Display Action Menu/Variable Keys Notes
1 Press 3 sec.
2 Password Set Password
3 Press
4 Main menu Select Unit parameters
5 Unit parameters Select Climatic TExt
6 Climatic TExt (pwd) Select Parameter
7Set
8 Conrm
9 Press 3 sec.
10 Select Local connections
Path: Main Menu / Unit parameters / Climatica TExt
Parameters Short description Description
P0265: CSptLow setpoint temperature value when the air temperature value is AirAtSptLowC
P0266: AirAtSptLowC external air temperature value where the calculated setpoint takes on the value given by SptLowC
P0267: CSptHigh setpoint temperature value when the air temperature value is AirAtSptHigC
P0268: AirAtSptHigC external air temperature value where the calculated setpoint takes on the value given by SptHigC

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the CLIVET WDAT-SL3 FC Series and is the answer not in the manual?

CLIVET WDAT-SL3 FC Series Specifications

General IconGeneral
BrandCLIVET
ModelWDAT-SL3 FC Series
CategoryChiller
LanguageEnglish

Related product manuals