Dimensional drawings - FCD conguration (Direct FREE-COOLING)
Size 200.2-210.2 -
Acoustic conguration
:
compressor soundproong
(SC
)
Size
SC-EXC
200.2 210.2
H (without Axitop) mm 2484 2484
Imm--
Jmm--
Kmm--
OD (water ttings diameter) 8’’ 8’’
A - Length mm 5316 5316
B - Depth mm 2246 2246
C - Height mm 2668 2668
W1 Supporting point kg 1637 1649
W2 Supporting point kg 1387 1394
W3 Supporting point kg 1664 1673
W4 Supporting point kg 1414 1418
Shipping weight kg 5431 5462
Operating weight kg 6102 6134
The presence of optional accessories may result in a substantial variation of the weights shown in the table. Fan diusers are separately supplied.
1. Internal exchanger (evaporator)
2. External exchanger (condenser)
3. Unit xing holes
4. Lifting brackets (removable, if required, after the unit positioning)
5. Electrical panel
6. Power input
7. Sound proof enclosure ( only in the relevant versions)
8.
Clearance access recommended