24 WDAT-SL3 FC 200.2-580.2 M08S40E15-01
6.13 ECOSHARE function for the automatic management of a group of units
Max 7 units
Maximum length of the bus line: 1000 m.
Maximum distance between 2 units: 700 m.
Type of cable: shielded twisted pair cable Ø 0,8 mm. use an EIB/KNX cable
Possible connections: Tree, star, in/out bus, mixed
It is not possible to use a ring connection
No end-of-line resistor or terminator required
There must be suitable arresters to protect the serial lines from the eects of atmospheric discharges
The data line must be kept separate from the power conductors or powered at dierent voltage values and away from possible sources
of electrical interference