34 WDAT-SL3 FC 200.2-580.2 M08S40E15-01
8.3 Unit booklet
Its advisable to create a unit booklet to take notes of the unit interventions.
In this way it will be easier to adequately note the various interventions and aid any troubleshooting.
Report on the booklet:
date
type of intervention eected
intervention description
carried out measures etc.
8.4 Standby mode
If a long period of inactivity is foreseen:
turn o the power
avoid the risk of frost (empty the system or add glycol)
Turn o the power to avoid electrical risks or damages by lightning strikes.
With lower temperatures keep heaters turned on in of the electrical panel (option).
Its recommended that the re-start after the stopping period is performed by a qualied technician, especially after seasonal stops or seasonal
switching.
When restarting, refer to what is indicated in the “start-up” section.
Schedule technical assistance in advance to avoid hitches and to guarantee that the system can be used when required.
8.5 Water side exchanger
It is very important for the exchanger to be able to provide the maximum thermal exchange, therefore it is essential for the inner surfaces to
be clean of dirt and incrustations.
Periodically check the dierence between the temperature of the supply water and the condensation temperature: if the dierence is greater
than 8°C–10°C it is advisable to clean the exchanger.
The clearing must be eected:
with circulation opposite to the usual one
with a speed at least 1,5 times higher than the nominal one
with an appropriate product moderately acid (95% water + 5% phosphoric acid)
after the cleaning rinse with water to inhibit the action of any residual product
8.6 Water lter
Check that no impurities prevent the correct passage of water.
8.7 Circulating pumps
Check:
no leaks
bearing status (anomalies are highlighted by abnormal noise and vibration)
the terminal protection covers are closed and the cable holders are properly positioned
8.8 Flow Switch
controls the operations
remove incrustations from the palette
8.9 Electric fans
Check:
the fans and the relative protection gridsare well xed
the fan bearings (evident by noise and anomalous vibrations)
the terminal protection covers are closed and the cable holders are properly positioned

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the CLIVET WDAT-SL3 FC Series and is the answer not in the manual?

CLIVET WDAT-SL3 FC Series Specifications

General IconGeneral
BrandCLIVET
ModelWDAT-SL3 FC Series
CategoryChiller
LanguageEnglish

Related product manuals