TROUBLESHOOTING
112
Hd
Description
Communication error between master unit and slave unit(s) (in parallel)
The unit shuts down.
The error code is displayed on the water circuit PCB, main PCB and user interface.
Possible causes
SW9 DIP switch with incorrect settings
More than two units are connected to the wired controller
The switch-on interval between the master unit and the slave unit is longer than 2 minutes
Wire connection error
Unstable communication between the units
Address code missing or address code setting duplicated
The main board fuse is damaged BH