113
TROUBLESHOOTING
Hd
SW9 DIP switch with incorrect settings
YES
Check SW9 setting. Master unit: ON; Slave unit:
OFF
NO
More than two units are connected to the wired
controller
YES
Ensure only one controller is connected
Master unit.
NO
The switch-on interval between the master unit and
the slave unit is longer than 2 minutes
YES
Ensure the switch-on interval between the master
unit
and the slave unit is less than 2 minutes
NO
Wire connection problem
YES
Reconnect the wire according to the group control
wiring diagram for the system in part 2. Ensure the
wires
are connected eectively and without strong
electricity
or strong magnetic interference.
NO
Unstable communication between the units
YES
Add the corresponding network wire from port H1
or
H2 to the communication system terminal
NO
Address code missing or address code setting
duplicated
YES
Reset the address code from another control
NO
The main board fuse is damaged
YES
Replace the main board

Other manuals for CLIVET WiSAN-YME 1 S 8.1

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the CLIVET WiSAN-YME 1 S 8.1 and is the answer not in the manual?

CLIVET WiSAN-YME 1 S 8.1 Specifications

General IconGeneral
BrandCLIVET
ModelWiSAN-YME 1 S 8.1
CategoryHeat Pump
LanguageEnglish

Related product manuals