EasyManuals Logo

CLIVET WiSAN-YME 1 S 8.1 Service Manual

CLIVET WiSAN-YME 1 S 8.1
120 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #57 background imageLoading...
Page #57 background image
57
TROUBLESHOOTING
E1
Description
Phase sequence error.
Applies to three-phase models only.
The unit shuts down.
The error code is displayed on the main PCB and user interface.
Possible causes
Power supply phases not connected in the correct sequence.
Loosened power supply terminals.
Abnormal power supply.
Main PCB is damaged.