Compact controller ER 2022S and ER 2022SA
8. Configuration
8.6 Binary functions “binF”
Controller off (controller outputs are switched off)
Display “off” with key inhibit
Acknowledge limit comparators
The parameter and configuration levels are inhibited.
In addition, the start of autotuning is inhibited
The signal is active after approx. 1 second (pulse)
If the binary functions are active, a configurable text is
shown in the lower display. The text can be uniquely
defined (only through the setup program)
NOTE: Factory settings shown with BOLD text
parameter set
switching
A binary function can be used to switch between set point 1 and set point 2 or parameter set
1 and parameter set 2.
In order to switch between the four possible set points, two binary functions must be
configured to set point switching. The stats of the two binary functions are designated Z1 ab
z” and switch the set points over as shown in the table below.
0 = contact open/OFF - 1 = contact closed/ON