EasyManua.ls Logo

Clorius Controls ER 2022S - Technical Data

Clorius Controls ER 2022S
69 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Compact controller ER 2022S and ER 2022SA
www.clori uscontrols.com
60 of 69
12. Technical data (appendix)
Thermocouple input
Designation Measuring range
Measuring
accuracy
Ambient
temperature error
Fe-Con L
-200 to + 900°C
0.25%
100 ppm /°C
Fe-Con J EN 60 584
-200 to +1200°C
0.25%
100 ppm /°C
Cu-Con U
-200 to + 600°C
0.25%
100 ppm /°C
Cu-Con T EN 60 584
-200 to + 400°C
0.25%
100 ppm /°C
NiCr-Ni K EN 60 584
-200 to +1372°C
0.25%
100 ppm /°C
NiCr-Con E EN 60 584
-200 to +1000°C
0.25%
100 ppm /°C
NiCrSi-NiSi N EN 60 584
-100 to +1300°C
0.25%
100 ppm /°C
Pt10Rh-Pt S EN 60 584
0 to 1768°C
0.25%
100 ppm /°C
Pt13Rh-Pt R EN 60 584
0 to 1768°C
0.25%
100 ppm /°C
Pt30Rh-Pt6Rh B EN 60 584
0 to 1820°C
0.25%
1
100 ppm /°C
W5Re-W26Re C
0 to 2320 °C
0.25%
100 ppm /°C
W3Re-W25Re D
0 to 2495 °C
0.25%
100 ppm /°C
W3Re-W26Re
0 t o 2400 °C
0.25%
100 ppm /°C
Cold junction
Pt100,
internal
1. in the range 300 to 1820°C
Input for resistance thermometer
Designation Connection Measuring range
Measuring
accuracy
Ambient
temperature error
3-/4-wire
2-wire
Pt100 EN 60 751
2-wire / 3-wire / 4-wire
-200 to +850°C
0.05%
0.4%
50 ppm / °C
Pt500 EN 60 751
2-wire / 3-wire / 4-wire
-200 to +850°C
0.2%
0.4%
100 ppm /°C
Pt1000 EN 60 751
2-wire / 3-wire / 4-wire
-200 to +850°C
0.1%
0.2%
50 ppm /°C
KTY11-6
2-wire
-50
to +150°C
1.0%
2.0%
50 ppm /°C
Sensor lead resistance
max. 30
per lead for 3-wire or 4-wire circuit
Measuring current
approx. 250µA
Lead compensation
Not required for 3-wire or 4-wire circuit. With a 2-wire circuit, the lead resistance can
be
compensated in software by a correction of the process value.
Input for standard signals
Designation Measuring range
Measuring
accuracy
Ambient
temperature error
Voltage
0(2) 10V
0 — 1V
input resistance R
IN
> 100k
0.05%
0.05%
100 ppm /
°C 100
ppm / °C
Current
0(4)20mA, voltage drop 1.5V
0.05%
100 ppm / °C
Heating current
0 — 50mA AC
1%
100 ppm / °C
Resistance transmitter
min. 100, max. 4k
0.5%
100 ppm / °C
Binary inputs
Standard version
Floating contacts