IGS-NT Combi, SW Version 3.0,   ©ComAp – May 2013                    
IGS-NT-Combi-3.0 Reference Guide.PDF 
 
 
NOTE:  
If more then one binary input for MinRunPower is activated, the one with the 
highest number is used (i.e. its corresponding value).  
 
CAUTION!  
All controllers cooperating together in Power management must have the same 
minimal running power selected. 
 
NOTE:  
It is possible to use virtual peripheries for distribution of the binary signal from one 
physical switch connected to one controller to all other controllers over the CAN 
bus. See the principial diagram of such distribution in the description of the input 
Load res 2.  
 
 
Binary input: MinRun power 3 
This input is used to activate the function Minimal running power #3, which is 
adjusted by setpoint #MinRunPower 3. 
NOTE:  
The default value of minimal running power, which takes place while none of the 
inputs MinRun power x, is 0kW.  
 
NOTE:  
If more then one binary input for MinRunPower is activated, the one with the 
highest number is used (i.e. its corresponding value).  
 
CAUTION!  
All controllers cooperating together in Power management must have the same 
minimal running power selected. 
 
NOTE:  
It is possible to use virtual peripheries for distribution of the binary signal from one 
physical switch connected to one controller to all other controllers over the CAN 
bus. See the principial diagram of such distribution in the description of the input 
Load res 2.  
 
 
Binary input: Priority sw A 
This is one of four inputs Priority sw A, Priority sw B, Priority sw C and Priority sw 
D that can be used for selection of the power management priority externally. 
These inputs are optional and if not configured, the priority is then adjusted by the 
setpoint Priority. 
ENCODING TABLE