IGS-NT Combi, SW Version 3.0,   ©ComAp – May 2013                    
IGS-NT-Combi-3.0 Reference Guide.PDF 
 
description of the GCB close/open output. 
There are also other outputs availabe for MCB control:  
  MCB close/open 
  MCB OFF coil 
  MCB UV coil 
 
 
Binary output: MCB OFF Coil 
This output is intended for opening of the MCB using OFF coil if a circuit breaker 
is used as MCB. The output provides 2 sec pulse when the MCB has to open. If 
synchronizing is disabled with the particular breaker, the pulse length is extended 
to 5sec. See timing diagram of all available breaker control outputs in the 
description of the GCB close/open output. 
There are also other outputs availabe for MCB control:  
  MCB close/open 
  MCB ON coil 
  MCB UV coil 
 
 
Binary output: MCB UV Coil 
This output is intended for opening of the MCB using an undervoltage coil if a 
circuit breaker is used as MCB.  
  The output is closed while mains values are within limits. MCB closing 
command is blocked for 1 sec after the UV coil has been closed to allow 
the breaker mechanical system getting ready for closing.  
  The output is opened for 2 sec when the MCB has to open. If 
synchronizing is disabled with the particular breaker, the length of the 
inverse pulse is extended to 5sec.