This setpoint adjusts the rate pre second at which the ExtValue 2 is beeing
changed while the input ExtValue2 up or ExtValue2 down is active.
This setpoint adjusts the reset (initial) value of the ExtValue 3. This initial value is
applied either when the controller is powered-on or when the ExtValue 3 is reset
by the binary input ExtValue3reset.
-32000 .. ExtValue3HiLim [X]
This setpoint adjusts the low limit of the value of ExtValue 3 if the value is
lowered/raised by the binary inputs ExtValue3 up and ExtValue3 down. The
ExtValue 3 is never lowered below this limit.
NOTE:
This limit is not taken into account if the value ExtValue 3 is written remotely from
a terminal using the appropriate command ExtValue #n.
NOTE:
For IS-NT only.
ExtValue3LoLim .. 32000 [X]
This setpoint adjusts the high limit of the value of ExtValue 3 if the value is
lowered/raised by the binary inputs ExtValue3 up and ExtValue3 down. The
ExtValue 3 is never raised over this limit.
NOTE:
This limit is not taken into account if the value ExtValue 3 is written remotely from
a terminal using the appropriate command ExtValue #n.
NOTE:
For IS-NT only.