 PWR, SW version 1.0, ©ComAp – March 2009                30 
IA-NT- PWR-1.0-Reference Guide R1.pdf 
Remote OFF 
If closed, IA-NT is switched to OFF mode (there are four modes OFF-MAN-AUT-TEST). When opens 
controller is switched back to previous mode. 
 
NOTE:  
This binary input should be connected to schedule timer switch, to avoid start of engine. 
Remote MAN 
If the input is active, MAN mode is forced to the controller independently on the position of the MODE 
selector.  
Remote AUT 
If the input is active, AUTO mode is forced to the controller independently on the position of the MODE 
selector. If another of remote inputs is active, then the REMOTE AUT input has the lowest priority.  
Remote TEST 
If closed, IA-NT is switched to TEST mode (there are four modes OFF-MAN-AUT-TEST). When opens 
controller is switched back to previous mode. 
Rem TEST OnLd 
Affects the behavior in TEST mode. When input is closed, the controller automatically transfers load 
from the mains to the gen-set. Setpoint AMF Settings: ReturnFromTEST must be set to MANUAL. 
Load is automatically transferred back to the mains when any gen-set shut down protection activates.  
RemControlLock 
If the input is active, setpoints writing or command sending from the external terminal is disabled.  
FaultResButton 
Binary input has the same function as Fault Reset button on the InteliATS
NT
 front panel.  
GCB Button 
Binary input has the same function as GCB   button on the InteliATS
NT
 front panel. It is active in MAN 
mode only.  
MCB Button 
Binary input has the same function as MCB   button on the InteliATS
NT
 front panel. It is active in MAN 
mode only.  
MainsFailBlock 
If the input is closed, the automatic start of the gen-set at Mains failure is blocked. In case of running 
gen-set the GCB is opened, gen-set goes to Cooling procedure and stops. 
GenReadyToLoad 
Indicates wether the gen-set is ready to undertake load. Conditions for successful gen-set start and 
readiness to undertake load can be – depending on the GenerProtect setpoint – evaluated from the 
voltage and the frequency of the generator or from the state of GenReadyToLoad input. The 
conditions have to be fulfilled during time defined by the MaxGenStartDel setpoint (which can be even 
unlimited). More info can be found in the setpoint description.  
Neutral Pos 
In MAN mode this input switches a three position ATS switch to its neutral position – it activates the 
binary output NeutralPosition and switches the MCB and GCB off.