Loading...
InteliATS
NT
PWR, SW version 1.0, ©ComAp – March 2009 56
IA-NT- PWR-1.0-Reference Guide R1.pdf
History file
InteliATS
NT
stores a record of each important event into the history file. The history file seats 117
records. When the history file is full, the oldest records are removed.
NOTE:
To force history download in LiteEdit (direct, modem or Internet) open History window and select
History | Read history command.
Record structure
Abbreviation Historical value
Num Number of historical event
Reason Event specification
Date Date of historical event in format DD/MM/YY
Time Time of historical event in format HH:MM:SS
Mode Controller’s mode
Pwr Generator active power
PF Generator PF
LChr Character of the load
Gfrq Generator frequency
Vg1 Generator voltage L1
Vg2 Generator voltage L2
Vg3 Generator voltage L3
Ig1 Generator current L1
Ig2 Generator current L2
Ig3 Generator current L3
Vm1 Mains voltage L1
Vm2 Mains voltage L2
Vm3 Mains voltage L3
Mfrq Mains frequency
UBat Battery voltage
BIN Binary inputs IA-NT
BOUT Binary outputs IA-NT

Table of Contents

Related product manuals