GenStart Logic [CLOSE-ON/CLOSE-OFF]
The set point influences the behavior of the output Gen Start/Stop.
CLOSE-ON: Gen-set should start when the output Gen Start/Stop is closed.
CLOSE-OFF: Gen-set should start when the output Gen Start/Stop is opened.
Batt Undervolt [V]
Warning threshold for low battery voltage.
Step: 0,1 V
Range: 8V – 40 (Battery >Volts)
Batt Overvolt [V]
Warning threshold for hi battery voltage.
Step: 0,1 V
Range: 8V – 40 (Battery <Volts)
Batt Volt Del [s]
Delay for low battery voltage alarm.
Step: 1s
Range: 0 – 600 s
Engine Params
Prestart Time [s]
Time of closing of the Prestart and/or Pretransfer output prior to the engine start.
Set to zero if you want to leave the output Prestart/Pretransfer open.
Step: 1s
Range: 0 – 600 s
Cooling Time [s]
Runtime of the unloaded gen-set to cool the engine before stop.
Step: 1s
Range: 0 – 3600 s
Max Start Del [s]
This timeout starts after closing binary output GEN START/STOP. When generator does not reach
defined limits Basic Settings: Nominal Freq) within Max Start Del, Trp Start Fail alarm occurs and the
gen-set will shut down. See the table below for a description of the engine start evaluation.
If MaxStartDel is longer then 600 s it means there is NO TIMEOUT.
Step: 1s
Range: 0 – 600 s, 601 s = NO TIMEOUT