InteliATS
NT
PWR, SW version 1.0, ©ComAp – March 2009 37
IA-NT- PWR-1.0-Reference Guide R1.pdf
GenStart Logic [CLOSE-ON/CLOSE-OFF]
The set point influences the behavior of the output Gen Start/Stop.
CLOSE-ON: Gen-set should start when the output Gen Start/Stop is closed.
CLOSE-OFF: Gen-set should start when the output Gen Start/Stop is opened.
Batt Undervolt [V]
Warning threshold for low battery voltage.
Step: 0,1 V
Range: 8V – 40 (Battery >Volts)
Batt Overvolt [V]
Warning threshold for hi battery voltage.
Step: 0,1 V
Range: 8V – 40 (Battery <Volts)
Batt Volt Del [s]
Delay for low battery voltage alarm.
Step: 1s
Range: 0 – 600 s
Engine Params
Prestart Time [s]
Time of closing of the Prestart and/or Pretransfer output prior to the engine start.
Set to zero if you want to leave the output Prestart/Pretransfer open.
Step: 1s
Range: 0 – 600 s
Cooling Time [s]
Runtime of the unloaded gen-set to cool the engine before stop.
Step: 1s
Range: 0 – 3600 s
Max Start Del [s]
This timeout starts after closing binary output GEN START/STOP. When generator does not reach
defined limits Basic Settings: Nominal Freq) within Max Start Del, Trp Start Fail alarm occurs and the
gen-set will shut down. See the table below for a description of the engine start evaluation.
If MaxStartDel is longer then 600 s it means there is NO TIMEOUT.
Step: 1s
Range: 0 – 600 s, 601 s = NO TIMEOUT

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliATS NT PWR and is the answer not in the manual?

ComAp InteliATS NT PWR Specifications

General IconGeneral
BrandComAp
ModelInteliATS NT PWR
CategoryController
LanguageEnglish

Related product manuals