InteliATS
NT
PWR, SW version 1.0, ©ComAp – March 2009 45
IA-NT- PWR-1.0-Reference Guide R1.pdf
Time [HHMMSS]
Real time clock adjustment.
Date [DDMMYYYY]
Actual date adjustment.
Timer 1..2 Repeat
[NONE/MONDAY/TUESDAY/WEDNESDAY/THURSDAY/WEDNESDAY/FRI
DAY/SATURDAY/SUNDAY/MON-FRI/MON-SAT/MON-SUN/SAT-SUN]
Defines TIMER 1 activation. Binary output TIMER 1 is internally linked with Rem Start/Stop binary
input. Refer to binary inputs for details.
NONE: Timer function is disabled
MONDAY, TUESDAY, WEDNESDAY, THURSDAY, WEDNESDAY, FRIDAY, SATURDAY, SUNDAY:
Timer is activated on daily basis.
MON-FRI, MON-SAT, SAT-SUN:
Timer is activated on selected day interval.
Timer1..2 ON Time
Day time when Timer output activates.
Timer1..2Duration
Duration of Timer output is active.
Step: 1 min
Range: 1 – 1440 s
SMS/E-Mail
Remote alarm messaging
If a GSM modem and/or Internet Bridge is connected to the controller, the controller can send SMS
messages and/or emails in the moment when a new alarm appears in the Alarm list. The message will
contain a copy of the Alarm list.
To enable this function, you should select with setpoints Yel Alarm Msg and Red Alarm Msg, which
levels of alarms shall be announced (red/yellow/both) and also enter valid GSM phone number and/or
e-mail address to the setpoints TelNo/Addr Ch1 and TelNo/Addr Ch2. It is possible to put either a
GSM number or e-mail to both setpoints.
NOTE:
An internet module must be available for sending of e-mails. Similarly, a GSM modem is necessary for
sending of SMS.
NOTE:
There are 5 attempts for any active call (SMS/E-Mail). Timeout for connection is 90 sec and after 120
sec controller starts the next attempt. During the time the IA-NT is trying to send an active call type,
incoming calls are blocked.
Yel Alarm Msg [DISABLED, ENABLED]
Set this setpoint to YES if you want to get messages when a yellow (warning) alarm occurs.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliATS NT PWR and is the answer not in the manual?

ComAp InteliATS NT PWR Specifications

General IconGeneral
BrandComAp
ModelInteliATS NT PWR
CategoryController
LanguageEnglish

Related product manuals