EasyManua.ls Logo

ComAp InteliATS NT PWR - Alarm Message Configuration and Target Addresses

ComAp InteliATS NT PWR
69 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
InteliATS
NT
PWR, SW version 1.0, ©ComAp – March 2009 46
IA-NT- PWR-1.0-Reference Guide R1.pdf
NOTE:
The target address (GSM phone number or e-mail address) must be set correctly to the setpoint(s)
TelNo/Addr Ch1 resp. TelNo/Addr Ch2.
Red Alarm Msg [DISABLED, ENABLED]
Set this setpoint to YES if you want to get messages when a red (shutdown) alarm occurs.
NOTE:
The target address (GSM phone number or e-mail address) must be set correctly to the setpoint(s)
TelNo/Addr Ch1 resp. TelNo/Addr Ch2.
TelNo/Addr Ch1, 2
Enter either a valid GSM phone number or e-mail address to this setpoint, where the alarm messages
shall be sent. Type of active call is considered from the value of this parameter. If it consist „@“ it is
supposed to be e-mail address and active e-mail is sent. If the value is number, without „@“, it is
supposed to be the telephone number and active SMS is sent.
NOTE:
For GSM numbers use either national format (i.e. like number you will dial if you want to make a local
call) or full international format with "+" character followed by international prefix in the begining.
This setpoint can be modified from PC only!