3.11. U10> 10-minute average - voltage quality
The 11th menu item shows the parameterization of U10> 10-minute aver-
age - voltage quality.
Trip: Trigger - activate/deactivate the function.
Trip V: Switching point 10-minute average value that leads to a trig-
ger when overshot.
Hyster: Hysteresis - undershooting of the switching point minus the
hysteresis leads to a relapse.
Delay: Trigger time - duration for which the switching point must be
overshot so that it leads to a trigger.
Return: Relapse time - duration for which the switching point must be
undershot so that it leads to a relapse.