FAX: + 43 / 1 / 813-64-21-21
Homepage: http://www.compactelectric.at
3.16.
3.17. Vk> vector shift
The 17th menu item shows the parameterization of Vk> vector shift.
Trip: Trigger - activate/deactivate the function.
Angle: Switching point - phase angle, which must occur at least during a
vector shift so that it leads to a trigger.
Logic: Trigger logic - if L1|2|3 are set, the vector shift trigger is single
phase sensitive; if L1+2+3 are selected, the switching point for all
three phases must be overshot.
tBlock: Blockade time - the vector shift trigger is blocked for the set block-
ing time after the auxiliary voltage has been switched on and after
the relay has relapsed to the OK state.
tPulse: Pulse time - the duration of the vector shift trigger signal is varia-
ble and can be set using the tPulse parameter.