32 Installation
4.3 Positioning and mounting the central unit
Positioning the central unit
The central unit is designed for wall-mounting in interior spaces. Make sure that the construction (duct
wall, pillar, etc.) to which the central unit is to be mounted, offers a sufciently high load-bearing
capacity, and is suitable for the installation.
CAUTION!
Do not mount the central unit to vibrating components, not in exposed areas or places with exces-
sive dust load.
The central unit may only be installed in rooms with a oor drain. If for some reason the central unit
must be installed in a location without oor drain, it is mandatory to provide a leakage monitoring
device to safely interrupt the water supply in case of leakage. Additionally make sure that in case of
a water leakage not material assets can be damaged.
Locate the central unit in such a manner that:
the length of the spray circuit lines between central unit and housing feed throughs of the duct
are as short as possible (max. 10 m).
the spray circuit lines can be installed with a constant downslope (min. 2%) from the housing
feed throughs on the duct/AHU to the connections of the central unit.
the central unit is freely accessible with sufcient space available for maintenance purposes
(minimum distances showed in the following illustration must be adhered to).
the control unit can be mounted in direct proximity to the central unit (max. length of the electri-
cal connecting cables between control unit and central unit 0.75 m)
The central unit is protected according to IP22. Make sure the central unit are installed in a drip-proof
location and the admissible ambient conditions are complied with.
When xing the central unit use only the xing materials supplied with the unit. If xing with the
materials supplied is not possible in your particular case, select a method of xing that is of similar
stability.