EMS-96 Instruction Manual IM1200-U v1.6 Pag. 48 / 48
RS485 half-duplex with optical isolation
4.8 - 9.6 - 19.2 - 38.4 - 57.6 - 115.2 kbps
Profibus with slave DP-V0
0.3 - 0.6 - 1.2 - 2.4 - 4.8 - 9.6 - 19.2 - 38.4 kbps
Input rated voltage V
INPUT
24, 48, 115, 230 Vac/dc (only one defined in the order)
Rated input current I
INPUT
@ V
INPUT
: 5mA
MAX
@ V
INPUT
=all voltages
2 terminals (A-K) for each input: NPN, PNP
T
ON_min
30ms, T
OFF_min
30ms
Number of digital outputs
Photo-MOS (solid state); RON= 8 typ. (12 MAX)
10÷300Vdc 150mA
MAX
; 12÷250Vac 150mA
MAX
Digital Output programmed as alarm
Selectable pulse period 60ms÷1000ms
Programmable pulse polarity (active close or active open)
Programmable pulse “weight”
T
ON_min
30ms, T
OFF_min
30ms
Maximum lenght of connection
0÷10V or -10÷10V or 0÷5V or -5÷5V
Max: 0.5% on E.S. – Typical 0.2% on E.S.
Max: 0.3% on E.S. – Typical 0.1% on F.S.
Linearity: 0.01 on F.S. - Thermal stability: 0.01 on F.S.
50µs(0÷20mA)@R
LOAD
=1K , C
LOAD
=200pF, L
LOAD
=1mH
50µs(-10 ÷10V)@R
LOAD
=1K , C
LOAD
=200pF
Hours, minutes, seconds, day of week, date, month, year
Through modbus command and keys
Retention (in absence of voltage)
CE COMPLIANCE AND STANDARDS
The instrument was tested in compliance with EMC 89/336/EEC and complies with the following standards:
EMISSIONS = EN 50081-2, 1992 - EN 55022-CLASS B CISPR 22
IMMUNITY = EN 50082-1, 1992 - EN 61000-6-2
SAFETY = EN 61010-2