Commander SE User Guide
Issue Number 5 63
11.2.3Commander SE Size 3, 200V product
Conformity
The Drive conforms to UL listing requirements only when the following is observed:
UL listed class J 35A fast acting fuses e.g. Gould Amp-Trap A4J35, Littelfuse
Power Gard JLS35 or equivalent are used in the AC supply.
11.2.4Commander SE Size 3, 400V product
Conformity
The Drive conforms to UL listing requirements only when the following is observed:
UL listed class CC fast acting fuses e.g. Bussman Limitron KTK series, Gould
Amp-Trap ATM series or equivalent are used in the AC supply.
11.2.5Commander SE Size 4
Conformity
The Drive conforms to UL listing requirements only when the following is observed:
UL listed class J 40A fast acting fuses e.g. Gould Amp-Trap A4J40, Littelfuse
Power-Gard JLS40 or equilvalent are used in the AC supply.