1018029-E Page 22
TROUBLESHOOTING CHART ( SPECIFICALLY FOR INTERMITTENT IGNITION SYSTEM ) - IID
OFF No Call for Heat Not Applicable None
Normal Operation
Heartbeat
Not Applicable None

Flame failed
during run
3



If system fails to light on next trial ignition, check gas


Flame sense
leakage to ground
7 
fault corrects, control resumes normal
operation after a one minute delay.


rod ceramic for cracks, damage or tracking.

Delay - On every
third retry on the

6 + 2 
delay completed.


ground connection.
Flame sensed out
of sequence - longer
than 10 seconds
6 + 4 
sensed and then goes to soft lockout.
Flash code continues. Control auto resets
from soft lockout after one hour.


repeats, replace control.

voltage supply -

8

fault corrects, control resumes normal
operation after a one minute delay.
Check transformer and AC lines for proper input voltage

transformer.


run on the same

6 + 3

for ignition.


Startup - Flame
Sense Calibration
Flash Fast
Not Applicable None

Pilot ame not
detected during
trial for ignition
2

delay completed.
If system fails to light on next trial for ignition check


connection.
Flame sensed
out of sequence
4

seconds, control returns to normal

remains longer than 10 seconds, control



repeats, replace control.
Soft lockout due
to error detected
during self check
sequences
ON
Control auto resets from soft lockout after
one hour.

the control.
GREEN LED FLASH
CODE (XXY)ª
INDICATES NEXT SYSTEM ACTION RECOMMENDED SERVICE ACTION
Please follow the following corrective actions in order.