107
Other Parameters
Setting Range
Parameter Name
Description
IEEE1547-2018
Rule21
ISO-NE
Min
Default
Max
Min
Default
Max
Min
Default
Max
1: Enable
Island Protect
Island
enable/disable
control
0: Disable
1: Enable
0
1
1
0
1
1
0
1
1
FAN Detect
Fan detection
enable/disable
control
0: Disable
1: Enable
0
1
1
0
1
1
0
1
1
OperationOverVol
Operating
overvoltage
protection value
100
120
135
100
120
135
100
120
135
VirtualDamping
The parameter of
Virtual Damping
0
0
5
0
0
5
0
0
5
Mppt1_OptVolLow
Lim
Mppt1 optimizer's
Voltage lower
limit
200
200
1500
200
200
1500
200
200
1500
Mppt1_OptVolUpLi
m
Mppt1 optimizer's
Voltage upper
limit
200
1000
1500
200
1000
1500
200
1000
1500
Mppt2_OptVolLow
Lim
Mppt2 optimizer's
Voltage lower
limit
200
200
1500
200
200
1500
200
200
1500
Mppt2_OptVolUpLi
m
Mppt2 optimizer's
Voltage upper
limit
200
1000
1500
200
1000
1500
200
1000
1500
Mppt3_OptVolLow
Lim
Mppt3 optimizer's
Voltage lower
limit
200
200
1500
200
200
1500
200
200
1500
Mppt3_OptVolUpLi
m
Mppt3 optimizer's
Voltage upper
limit
200
1000
1500
200
1000
1500
200
1000
1500

Table of Contents