79
3. PV Input Mode. This allows the user to read the inverter working mode
as Independent" or "Parallel" mode. The inverter is factory set in
Independent mode. If this needs to be set to Parallel contact CPS to
have this setting changed.
4. Neutral Line Setting. This option allows the user to select “Yes/No” if
a neutral conductor has been connected to the inverter. This setting
does not affect the operation of the inverter. When a neutral is installed
and “Yes” is selected, the inverter will display L-N measurements.
5. Communication Setting. This interface is used to set the Modbus ID
and Baud rate for communication. More information on this is found in
the “Commissioning” section.
6. Time. Press or to select the numerical value, then press
ENT to go to next option. e.g.: Year to Month, press ESC to go to last
option. e.g.: Month to Year. Finally Press the ENT key to confirm the
setting. Press more than 1 second to go to last position of the
number when setting the parameters. e.g: 2008 to 2008. Press
more than 1 second to go to the next position of the number when
setting the parameters. e.g: 2008 to 2008.
7. LCD Contrast Setting. Press or to increase/decrease the
LCD contrast. Press ENT to accept changes.
INSTRUCTION:
Please check with your local electric utility supply company before
selecting a grid standard. If the inverter is operated with an incorrect
grid standard, the electric utility supply company may cancel the
interconnection agreement.
Placing the inverter into operation before the overall system complies
with the national codes, rules and safety regulations of the application
is also not permitted.